Pipe DN Recommendation

System type automatically sets velocity limits (and, for Heating/Cooling, a verified friction-rate target). Fire systems require high velocity, heating/cooling are sized primarily on friction loss.
Switch to "Calculate from Heat Load" to size the pipe from kW + ΔT instead of typing m³/h directly. Only available when System Type is Heating/Cooling.
Total flow rate through the pipe
Heating or cooling capacity carried by this pipe
ΔT for heating/cooling systems (typically 20°C for heating, 5-6°C for chilled water — e.g. 80/60°C heating or 6/12°C chilled water)
Used only for density in the heat-load-to-flow conversion. Heating: 70-80°C, Chilled water: 6-12°C
Pipe material affects inner diameter and roughness
🔧
Smart Diameter Selection

This calculator recommends the optimal pipe diameter based on your system type and flow requirements.<br/><br/> Each system has specific velocity limits: <ul> <li><b>HVAC:</b> 0.5-1.5 m/s (noise control)</li> <li><b>Fire:</b> 2.0-6.0 m/s (emergency response)</li> <li><b>Water:</b> 0.6-2.0 m/s (balanced)</li> <li><b>Compressed Air:</b> 6-12 m/s (high velocity OK)</li> </ul>

Key Points:
  • System-specific velocity limits
  • Automatic standard pipe selection
  • Alternative options provided
  • Head loss calculation included
Calculation Steps:
  1. Enter all required parameters
  2. Click "Update Calculation"
  3. Review results and analysis
Formula Variables:
D Diameter (mm)
Q Flow Rate (m³/h)
V Velocity (m/s)
Re Reynolds (-)
f Friction Factor (-)