Fire Pump Room Calculator (NFPA 20)
Fire Pump Room — NFPA 20
Designs a duty + standby + jockey fire pump room per NFPA 20 (2019).
RATING: flow rounded up to the next standard rating of Table 4.28(b); pumps are rated on NET pressure (discharge − suction).
PERFORMANCE (§6.2): churn ≤ 140 % of rated pressure; at 150 % flow ≥ 65 % of rated pressure.
PUMP ROOM PIPING (Table 4.28(b)): suction, discharge, relief valve and its discharge, flow meter, test header hose valves. Suction sizes are based on ≤ 4.6 m/s at 150 % flow.
OVER-PRESSURE: diesel — if 121 % of churn + max static suction exceeds the component rating, a relief valve is required (§4.20.1.2). Relief valves are only used where NFPA 20 permits them (§4.20.1.1).
JOCKEY (A.4.27.2.1): make up allowable leakage, at least 1 gpm (3.8 L/min), but less than one sprinkler.
SET POINTS (NFPA 20 Annex example): jockey stop = churn + min static; jockey start 0.68 bar lower; main pump start 0.34 bar lower; each additional pump 0.68 bar lower.
DIESEL FUEL TANK (§11.4.1.3.1): 5.07 L per kW + 5 % expansion + 5 % sump.
The pump curve is an ESTIMATE through churn and rated points — always confirm with the manufacturer's certified curve.
Key Points:
- NFPA 20 standard pump rating (Table 4.28(b))
- Pump room pipe sizes: suction, discharge, relief, meter, test header
- Churn ≤ 140 % and 150 % flow / 65 % pressure envelope
- Relief valve requirement check for diesel pumps
- Jockey pump sizing (less than one sprinkler)
- Jockey / main / standby pressure switch settings
- Driver power and diesel fuel tank volume